Exact Predictive Ventilation Control with Causal Occupancy Forecasts and Concentration Guarantees
Abstract
Predictive ventilation depends on both the mathematical plant and the information available when an airflow command is selected. We study these dependencies in a fully specified, single-zone apartment benchmark. For a well-mixed carbon dioxide balance with nonnegative generation and piecewise constant airflow, we derive an exact propagation map and prove that predicted concentration is jointly convex in the planned airflow sequence after the state variables are eliminated. The resulting finite-horizon problem retains the cubic fan law without successive linearization. A monotone one-step filter then enforces a selected concentration bound under declared occupancy and plant-parameter envelopes. We evaluate seven controllers on twelve independent, paired week-long simulations, using eight separate training weeks for occupancy-model estimation and reactive-controller tuning. Filtered Model Predictive Control (MPC) consumes 26.386 kWh/week of modeled fan-plus-heating energy, compared with 27.726 for the tuned rule and 28.965 for the original 1000/850 ppm rule. Its paired difference from the tuned rule is −1.340 kWh/week, with a pointwise 95% interval of [−1.465, −1.214]. A causal conditional-mean forecast with a five-minute occupancy-report delay yields only 0.045 occupants of one-step Mean Absolute Error (MAE), yet its unfiltered controller spends 44.175 minutes per occupied person-hour above 1000 ppm, predominantly through small exceedances. The filter removes these exceedances in the matched model at an added 0.037 kWh/week. Four paired mismatch tests show why the guarantee must use valid parameter envelopes. The results establish a reproducible separation between forecast quality, energy performance, and conditional concentration invariance; they do not constitute residential field validation or a general indoor-air-quality guarantee.
Keywords
Demand-controlled ventilation Exact discretization Convex optimization Causal occupancy forecasting Model predictive control Concentration invarianceReferences (31)
- [1] Fisk, W. J., & De Almeida, A. T. (1998). Sensor-based demand-controlled ventilation: A review. Energy and Buildings, 29(1), 35–45. https://doi.org/10.1016/s0378-7788(98)00029-2.
- [2] Persily, A., Bahnfleth, W. P., Kipen, H., Lau, J., Mandin, C., Sekhar, C., ..., & Weekes, L. C. N. (2022). ASHRAE position document on indoor carbon dioxide. ASHRAE, 64, 50-52. https://www.ashrae.org/file%20library/about/position%20documents/pd-on-indoor-carbon-dioxide-english.pdf
- [3] Persily, A., & de Jonge, L. (2017). Carbon dioxide generation rates for building occupants. Indoor Air, 27(5), 868–879. https://doi.org/10.1111/ina.12383.
- [4] Mayne, D. Q., Rawlings, J. B., Rao, C. V, & Scokaert, P. O. M. (2000). Constrained model predictive control: Stability and optimality. Automatica, 36(6), 789–814. https://doi.org/10.1016/s0005-1098(99)00214-9
- [5] Oldewurtel, F., Parisio, A., Jones, C. N., Gyalistras, D., Gwerder, M., Stauch, V., …, & Morari, M. (2012). Use of model predictive control and weather forecasts for energy efficient building climate control. Energy and Buildings, 45, 15–27. https://doi.org/10.1016/j.enbuild.2011.09.022
- [6] Li, B., Wu, B., Peng, Y., & Cai, W. (2022). Tube-based robust model predictive control of multi-zone demand-controlled ventilation systems for energy saving and indoor air quality. Applied Energy, 307, 118297. https://doi.org/10.1016/j.apenergy.2021.118297
- [7] Zhuang, C., Choudhary, R., & Mavrogianni, A. (2022). Probabilistic occupancy forecasting for risk-aware optimal ventilation through autoencoder Bayesian deep neural networks. Building and Environment, 219, 109207. https://doi.org/10.1016/j.buildenv.2022.109207
- [8] Jiang, Z., Deng, Z., Wang, X., & Dong, B. (2023). PANDEMIC: Occupancy driven predictive ventilation control to minimize energy consumption and infection risk. Applied Energy, 334, 120676. https://doi.org/10.1016/j.apenergy.2023.120676
- [9] Drgoňa, J., Arroyo, J., Figueroa, I. C., Blum, D., Arendt, K., Kim, D., ..., & Helsen, L. (2020). All you need to know about model predictive control for buildings. Annual Reviews in Control, 50, 190-232. https://doi.org/10.1016/j.arcontrol.2020.09.001
- [10] Killian, M., & Kozek, M. (2016). Ten questions concerning model predictive control for energy efficient buildings. Building and Environment, 105, 403–412. https://doi.org/10.1016/j.buildenv.2016.05.034
- [11] Kathirgamanathan, A., De Rosa, M., Mangina, E., & Finn, D. P. (2021). Data-driven predictive control for unlocking building energy flexibility: A review. Renewable and Sustainable Energy Reviews, 135, 110120. https://doi.org/10.1016/j.rser.2020.110120
- [12] Oldewurtel, F., Sturzenegger, D., & Morari, M. (2013). Importance of occupancy information for building climate control. Applied Energy, 101, 521–532. https://doi.org/10.1016/j.apenergy.2012.06.014
- [13] Candanedo, L. M., & Feldheim, V. (2016). Accurate occupancy detection of an office room from light, temperature, humidity and CO2 measurements using statistical learning models. Energy and Buildings, 112, 28–39. https://doi.org/10.1016/j.enbuild.2015.11.071
- [14] Caballero-Peña, J., Osma-Pinto, G., Rey, J. M., Nagarsheth, S., Henao, N., & Agbossou, K. (2024). Analysis of the building occupancy estimation and prediction process: A systematic review. Energy and Buildings, 313, 114230. https://doi.org/10.1016/j.enbuild.2024.114230
- [15] Lu, X., Pang, Z., Fu, Y., & O’Neill, Z. (2022). The nexus of the indoor CO2 concentration and ventilation demands underlying CO2-based demand-controlled ventilation in commercial buildings: A critical review. Building and Environment, 218, 109116. https://doi.org/10.1016/j.buildenv.2022.109116
- [16] Lu, X., Pang, Z., Fu, Y., & O’Neill, Z. (2022). Advances in research and applications of CO2-based demand-controlled ventilation in commercial buildings: A critical review of control strategies and performance evaluation. Building and Environment, 223, 109455. https://doi.org/10.1016/j.buildenv.2022.109455
- [17] Persily, A. (2022). Development and application of an indoor carbon dioxide metric. Indoor Air, 32(7), e13059. https://doi.org/10.1111/ina.13059
- [18] Naqvi, S., Kar, K., Bhattacharya, S., Chandan, V., Mishra, S., & Salsbury, T. (2023). Air quality and comfort constrained energy efficient operation of multi-zone buildings. Building and Environment, 244, 110716. https://doi.org/10.1016/j.buildenv.2023.110716
- [19] Andersen, A. H., & Jradi, M. (2025). Multi-objective optimization of building ventilation systems using model predictive control: integrating air quality, energy cost, and environmental impact. Applied Sciences, 15(1), 451. https://doi.org/10.3390/app15010451
- [20] Boyd, S. (1977). Convex optimization-boyd & vandenberghe. Journal on Numerical Analysis, 8, 6. https://web.stanford.edu/~boyd/cvxbook
- [21] Wabersich, K. P., & Zeilinger, M. N. (2021). A predictive safety filter for learning-based control of constrained nonlinear dynamical systems. Automatica, 129, 109597. https://doi.org/10.1016/j.automatica.2021.109597
- [22] Ames, A. D., Xu, X., Grizzle, J. W., & Tabuada, P. (2016). Control barrier function based quadratic programs for safety critical systems. IEEE Transactions on Automatic Control, 62(8), 3861–3876. https://doi.org/10.1109/tac.2016.2638961
- [23] Fisk, W. J. (2010). CO2 monitoring for demand controlled ventilation in commercial buildings. https://indoor.lbl.gov/publications/co2-monitoring-demand-controlled
- [24] Peng, Z., & Jimenez, J. L. (2021). Exhaled CO2 as a COVID-19 infection risk proxy for different indoor environments and activities. Environmental Science & Technology Letters, 8(5), 392–397. https://doi.org/10.1021/acs.estlett.1c00183
- [25] Rizo-Maestre, C., Flores-Moreno, J. M., Nebot Sanz, A., & Echarri-Iribarren, V. (2025). Intelligent ventilation and indoor air quality: state of the art review (2017-2025). Buildings, 16(1), 65. https://doi.org/10.3390/buildings16010065
- [26] Page, J., Robinson, D., Morel, N., & Scartezzini, J. L. (2008). A generalised stochastic model for the simulation of occupant presence. Energy and Buildings, 40(2), 83–98. https://doi.org/10.1016/j.enbuild.2007.01.018
- [27] Richardson, I., Thomson, M., & Infield, D. (2008). A high-resolution domestic building occupancy model for energy demand simulations. Energy and Buildings, 40(8), 1560–1566. https://doi.org/10.1016/j.enbuild.2008.02.006
- [28] Blum, D., Arroyo, J., Huang, S., Drgoňa, J., Jorissen, F., Walnum, H. T., ..., & Helsen, L. (2021). Building optimization testing framework (BOPTEST) for simulation-based benchmarking of control strategies in buildings. Journal of Building Performance Simulation, 14(5), 586-610. https://doi.org/10.1080/19401493.2021.1986574
- [29] Blum, D., Wang, Z., Weyandt, C., Kim, D., Wetter, M., Hong, T., & Piette, M. A. (2022). Field demonstration and implementation analysis of model predictive control in an office HVAC system. Applied Energy, 318, 119104. https://doi.org/10.1016/j.apenergy.2022.119104
- [30] Morris, T. P., White, I. R., & Crowther, M. J. (2019). Using simulation studies to evaluate statistical methods. Statistics in Medicine, 38(11), 2074–2102. https://doi.org/10.1002/sim.8086
- [31] Holm, S. (1979). A simple sequentially rejective multiple test procedure. Scandinavian Journal of Statistics, 65–70. https://www.ime.usp.br/~abe/lista/pdf4R8xPVzCnX.pdf